Emergency lighting and exit signs work hand-in-hand with evacuation diagrams. While diagrams show people where to go, emergency lighting ensures they can see the way, and exit signs confirm they are heading in the right direction. Together, these three elements form the visual evacuation guidance system for any building.
This guide covers the key requirements for emergency lighting and exit signs in Australian buildings.
Australian Standard AS 2293
Emergency lighting and exit signs in Australia are governed by AS 2293 (Emergency escape lighting and exit signs for buildings). The key requirements:
- Emergency lighting must illuminate evacuation routes to a minimum level so occupants can safely navigate to exits
- Exit signs must be illuminated at all times the building is occupied
- Emergency lighting must operate for at least 90 minutes on battery backup after mains power failure
- All escape routes, including corridors, stairways, ramps, and open areas, must have adequate emergency lighting
- The system must activate automatically on mains power failure
Types of Emergency Lighting
There are two main types of emergency luminaires:
- Maintained: the light is on at all times (same as normal lighting), with battery backup for power failure. Used in areas where lighting is needed continuously (cinemas, theatres, public areas).
- Non-maintained: the light is normally off and only activates when mains power fails. Used in areas that are normally well-lit and only need emergency illumination during blackout conditions (offices, corridors).
- Sustained: a combined fitting with normal and emergency lighting. The emergency lamp activates only on mains failure, while the normal lamp operates on mains power.
Exit Sign Requirements
Exit signs must comply with AS 2293 and show:
- The standard running man pictogram (green background, white figure)
- Directional arrow where the exit is not immediately visible
- Illuminated at all times (internally lit or externally illuminated)
- Positioned above exit doors and at every change of direction along the escape route
- Visible from the approach direction (not blocked by doors, signs, or decorations)
- Maintained and tested regularly
Testing and Maintenance
Emergency lighting systems must be tested regularly:
- Monthly: brief visual check that all lights and signs are operational (press test button for 1-2 seconds)
- Six-monthly: full discharge test (run on battery for 90 minutes, verify all lights maintain illumination)
- Annual: comprehensive inspection by a qualified electrician, including battery condition, charging circuit, and lamp replacement
- Records must be kept of all tests, including date, tester, results, and any deficiencies found
- Deficient luminaires must be repaired or replaced promptly
How Emergency Lighting Relates to Evacuation Diagrams
Emergency lighting and diagrams are complementary:
- Evacuation diagrams should be mounted near emergency lighting so they remain visible during power failure
- Exit routes shown on diagrams should correspond to the paths illuminated by emergency lighting
- If a diagram is displayed in an area without emergency lighting, it will be unreadable when it is needed most
- Consider illuminated diagram frames or photoluminescent diagrams for areas that may be dark during evacuation
Common Compliance Gaps
Fire inspectors frequently find these emergency lighting issues:
- Test buttons not pressed (no testing conducted since installation)
- Battery packs dead (lights do not activate on power failure)
- Exit signs obscured by tenant signage, displays, or decorations
- Exit signs pointing in the wrong direction after building renovation
- No testing records available for inspection
- Emergency lighting in fire stairs not covering all landings
Get Compliant Evacuation Diagrams
EvacPath creates evacuation diagrams that show emergency lighting and exit sign locations as part of the complete safety picture. Our diagrams include all fire safety equipment positions so occupants and wardens can see the full evacuation guidance system at a glance.
Print-ready PDFs delivered in 3 to 5 business days. Pricing starts at A$70 per diagram.
- Compliance
Evacuation Diagram Requirements: AS 3745 Australia Guide
Everything you need to know about AS 3745 evacuation diagram requirements in Australia, including size, placement, mandatory elements, costs.
- Compliance
AS 3745 vs NCC: Australian Emergency Compliance Guide
Confused about AS 3745 and the National Construction Code? This guide explains how they work together and what building owners need to know about emergency.
- Compliance
How Often Should Evacuation Diagrams Be Updated in Australia?
How often evacuation diagrams must be updated under AS 3745: the annual review, the printed validity date, change triggers, and amend vs redraw.
Free: AS 3745 compliance self-check
A short PDF that distills AS 3745 into the questions buyers actually ask before commissioning evacuation diagrams. Free, sent to your inbox, no sales follow-up.
Diagrams delivered in a week
EvacPath delivers AS 3745-aligned evacuation diagrams in 3 to 5 business days. No site visit.